Green Energy
AUTOMATIC VOLTAGE REGULATOR (AVR)
-I will talk today with you about an important equipment used in power system utilities, it is the Automatic Voltage Regulator (AVR). From its name it is a regulator which regulates the output voltage at a nominal constant voltage level.
Role of AVR
AVR (Automatic voltage regulator) has following roles.
1- To regulate generator terminal voltage.
Mainly generator under no-load condition, AVR regulates the generator voltage to voltage setter (90R).
*AVR detects terminal voltage and compare with voltage setter (90R).
*AVR regulates field current via the Exciter.
*Generator terminal voltage is regulated by field current.
Vt < 90R _ Field current will be increase
Vt > 90R _ Field current will be decrease
2-To adjust MVars (Reactive power).
When the generator connected to power grid, AVR adjust reactive power by regulate generator voltage.
MVar (Reactive power: Q) is regulated by generator terminal voltage. Therefore AVR can regulate MVars.
Vt is increased _ MVars will be increase
Vt is decreased _ MVars will be decrease
Hence;
To increase MVars _ 90R raise
To decrease MVars _ 90R lower
3-To improve the power system stability.
There are two stability
-Transient stability …… Improved by AVR
-Dynamic stability ……. Improved by PSS (power system stabilizer)
* Improve the Transient stability
Transient stability is improved by high initial response characteristic. In the fault condition, Field voltage is increased to keep the generator voltage constantly. If the excitation response is slow, it will not able to keep voltage and the generator cannot keep synchronizing.
* Improve the Dynamic state stability
Dynamic stability is improved by Power System Stabilizer (PSS). PSS is provided in order to improve the power system dynamic stability. PSS will control the excitation to reduce the power swing rapidly.
4-To suppress the over-voltage on load rejection.
When the load rejection, field current and field voltage should be reduced rapidly to keep terminal voltage constantly and prevent overvoltage.This information source is MELCO CO. for CEPC generator
-
How To Size Wire For Solar Panels
It is very important to size wires correctly for reaching energy from your solar panels to battery bank without any serious power loss. For example, we can say about flowing water through a pipe, if the size of the pipe is smaller, then very little amount...
-
Solar Charge Controller
Solar charge controller is a device which regulates voltage and/or current to protect batteries from overcharging in the solar photovoltaic system. It has been observed that most solar panels of 12 volts have output voltage of 16 to 20 volts approximately....
-
Generator Overvoltage Relay (59 G)
Generator Overvoltage Relay (59 G) Overvoltage shouldn’t occur on a generator fitted with an automatic voltage regulator. Overvoltage may be caused by defective operation of the voltage regulator under isolated operation of the generator. The...
-
Generator Stator Earth Fault Relay (64g) - 27tn.
Generator Stator Earth Fault Relay (64G) - 27TN. -For high impedance grounded generators, a voltage relay across the secondary winding of the generator neutral grounding transformer is used to detect the ground fault on the generator...
-
Phoenix Contact Introduces New Surge Protection Devices For 1,500 Volts
article originally published in www.sunwindenergy.com, on June 26th, 2015Large photovoltaic systems are increasingly using a higher operating voltage of 1,500 V, which makes transmitting the electricity to the inverter more cost-effective. Phoenix...
Green Energy