Generator over Fluxing Relay (24G)
Green Energy

Generator over Fluxing Relay (24G)



Generator over Fluxing Relay (24G)

-The relay measures the ratio of voltage to frequency (V/Hz) as this ratio is proportional to the flux-density level of the electromagnetic machine.
-Over Fluxing (Over Excitation) may be occur when a generator is on an isolated operation with the AVR in service and the generator speed decreasing from the synchronous speed.
-Over Fluxing may also be occurring when the utility system frequency decreases to a low value by any reason.






There are two sets of the V/Hz relays are provided for Generator Protection:-
A) Relay 24G (#2) for alarm
A definite time element #2 of the relay will be used to provide an alarm.

B) Relay 24G (#1 & INV) for trip
Operation of the relay 24G will trip the switchyard breaker.
An inverse time element of the relay will be used to provide a trip contact and a definite time element #1 is also used to further shape the protection curves.


Data for setting calculations

Short-time V/Hz withstand level at full load -----120%
Continuous V/Hz withstand level at full load-----105%
AVR V/Hz limiter setting -----------------------------105%



Setting of generator V/Hz alarm relay 24G (#2)
1)V/Hz alarm setting
Setting < continuous V/Hz withstand level at full load = 105 %

2)V/Hz alarm delay
Setting = 30 cycles (0.6 Sec.)


Setting of generator V/Hz alarm relay 24G (INV)
1) V/Hz trip setting for inverse time element
Setting = 107 %

2) V/Hz Reset rate for inverse time element
Reset rate = Practical recommendation is minimum setpoint of the relay
Setting = 1 Sec.
  
NOTE!! “If the generator is synchronized immediately after tripping by V/Hz relay operation, the generator will be damaged under V/Hz condition before limitation value. “



Setting of generator V/Hz alarm relay 24G (#1)
1)V/Hz alarm setting
Setting < short V/Hz withstand level at full load = 120 %

2)V/Hz alarm delay
Setting = 50 cycles (1 Sec.)




- Boiler (master Fuel Trip)
Steam Generator ( boiler ) is very important equipment at thermal power units , Boiler is the steam supply for the unit to rotate the turbine's rotor , hence produce electricity at Generator's stator. Boiler usually equipped with solar and Main...

- Turbine Supervisory Instruments
Turbine Supervisory Instruments The following supervisory instruments are furnished with the unit and are to be observed during start-up, operation and shutdown. We will explain the following instruments in detail as follows. 1- Casing ExpansionAs a...

- Generator Overvoltage Relay (59 G)
Generator Overvoltage Relay  (59 G) Overvoltage shouldn’t occur on a generator fitted with an automatic voltage regulator. Overvoltage may be caused by defective operation of the voltage regulator under isolated operation of the generator. The...

- Generator Stator Earth Fault Relay (64g) - 27tn.
Generator Stator Earth Fault Relay   (64G) - 27TN. -For high impedance grounded generators, a voltage relay across the secondary winding of the generator neutral grounding transformer is used to detect the ground fault on the generator...

- Generator Loss Of Excitation Relay (40g).
Electrical Generator Protection Relays. Electrical Generator is the main source of Electricity at Power Plant, we should make a many methods to protect the Generator from any faults can happen while Operation.The next figure shows the main single line...