Green Energy
Generator Loss of Excitation Relay (40G).
Electrical Generator Protection Relays.
Electrical Generator is the main source of Electricity at Power Plant, we should make a many methods to protect the Generator from any faults can happen while Operation.
The next figure shows the main single line diagram and Protection Scheme for the Generator.
The Generator made by Mitsubishi Heavy Industries (MHI) and its specification as follows:
Power-------------- 440 MVA
Power Factor----- 0.85 lag
Line Voltage------ 19 KV
Frequency--------50HZ
Speed-------------- 3000 rpm
Hydrogen (H2) Gas Cooled @ 4.5 barg.
Generator Loss of Excitation Relay (40G).
If a Synchronous machine losses the Excitation, the following condition will occur:
-When partial or complete loss of Excitation occurs on a synchronous generator, Reactive power flows from the other generator into the generator.
-The KW is controlled by the Prime-Mover input, while KVAR output is controlled by the Field Excitation. If the system is large enough to supply the deficiency in Excitation through the armature, the synchronous generator will operate as an induction generator, supplying essentially the same KW to the system as before the loss of Excitation.
-Since Synchronous generator is not designed for asynchronous operation, the machine output will oscillate slightly as the rotor oscillates in an attempt to lock into synchronism.
-Loss of Synchronism does not require immediate tripping unless there is an accompanying decrease in the terminal voltage that threatens system stability; it generally takes at least 2 to 6 Sec. to lose synchronism.
Data for setting calculations.
Generator capacity-------440000KVA
Generator Voltage--------19KVA
CT turns ratio-------------18000/5=3600
VT turns ration-----------19000/100=190
Gen. Transient impedance--------Xd’=24.8%
Gen. Synchronous impedance----Xd=195%
Relay setting calculations.
Relay Side Impedance
Z=Z% * ((KV2 * 10)/KVA) * (CT ratio/VT ratio)
Setting of small circle.
1-Circle #1 Diameter
Z=100 *((192*10)/440000)*(3600/190) = 15.55 Ω
2-Circle #1 Offset
Z=24.8 *((192*10)/440000)*(3600/190) = 1.93 Ω
3-Circle #1 Diameter
Setting=15 Cycles (0.3 Sec.)
Setting of large circle.
1-Circle #2 Diameter
Z=195 *((192*10)/440000)*(3600/190) = 30.31 Ω
2-Circle #2 Offset
Z=24.8 *((192*10)/440000)*(3600/190) = 1.93 Ω
3-Circle #1 Diameter
Setting=75 Cycles (1.5 Sec.)
-
Automatic Voltage Regulator (avr)
-I will talk today with you about an important equipment used in power system utilities, it is the Automatic Voltage Regulator (AVR). From its name it is a regulator which regulates the output voltage at a nominal constant voltage level.Role of AVRAVR...
-
Boiler (master Fuel Trip)
Steam Generator ( boiler ) is very important equipment at thermal power units , Boiler is the steam supply for the unit to rotate the turbine's rotor , hence produce electricity at Generator's stator. Boiler usually equipped with solar and Main...
-
Generator Overvoltage Relay (59 G)
Generator Overvoltage Relay (59 G) Overvoltage shouldn’t occur on a generator fitted with an automatic voltage regulator. Overvoltage may be caused by defective operation of the voltage regulator under isolated operation of the generator. The...
-
Generator Over Fluxing Relay (24g)
Generator over Fluxing Relay (24G) -The relay measures the ratio of voltage to frequency (V/Hz) as this ratio is proportional to the flux-density level of the electromagnetic machine.-Over Fluxing (Over Excitation) may be occur when a generator is...
-
Generator Stator Earth Fault Relay (64g) - 27tn.
Generator Stator Earth Fault Relay (64G) - 27TN. -For high impedance grounded generators, a voltage relay across the secondary winding of the generator neutral grounding transformer is used to detect the ground fault on the generator...
Green Energy